FAQ - Annunciator Panel
 
  Annunciator Panel - Questions
   


Q1.
How do I set the audible duration on the Annunciator panel?
Q2. What are the power and fusing requirements for the Annunciator Panel?


 




 

  Annunciator Panel - Answers
   

Q1 What input voltage is required to operate the Dual/Quad Modem shelf?

Mounted directly on the back of the audible annunciator device, the alarm timer module controls the duration of the audible alarm indication.

Note: The unit is shipped with the jumpers in the default (infinity) position.

The user sets the duration of audible alarm notification by placing a jumper on Z1, Z2, both, or none.

Z1
Z2
Timeout
OFF
OFF
2 seconds
OFF
ON
8 seconds
ON
OFF
16 seconds
ON
ON
Infinite (Continuous)
On - Jumper Installed; Off- Jumper Not Installed


Q2 What are the power and fusing requirements for the Annunciator Panel?

Input power (-20 Vdc to -72 Vdc, fused at 0.5 Amps) is applied to TB3. Pin 1 is +Batt, Pin 2 is -Batt, and Pin 3 is chassis ground.


 
 